Show simple item record

dc.contributor.advisorPinem, Maksum
dc.contributor.advisorRambe, Ali Hanafiah
dc.contributor.authorNasution, Agus Almi
dc.date.accessioned2021-07-05T07:33:52Z
dc.date.available2021-07-05T07:33:52Z
dc.date.issued2016
dc.identifier.urihttp://repositori.usu.ac.id/handle/123456789/34518
dc.description.abstractUsing non-linier load in Uninterruptible Power Supply (UPS) can cause harmonic distortion which will eventually have the effect on power quality. The research was designed as a single-turned passive filter to cope will harmonic distortion in UPS. In this phase, THDv, THDi, and IHDi were measured in UPS. MATLAB/Simulink was used for simulation of filter testing. After single-turned passive filter was installed, the third order of harmonic current decreased from 47,69% to 7,08% or reduced 40.61%.en_US
dc.description.abstractPenggunaan beban non linier pada Uninterruptible Power Supply (UPS) mengakibatkan distorsi harmonik yang berdampak pada kwalitas daya. Penelitian ini, dirancang sebuah single-tuned passive filter untuk mengatasi distorsi harmonik pada UPS. Pada tahapan ini dilakukan pengukuran THDv, THDi, dan IHDi pada UPS. Simulasi ujicoba filter menggunakan MATLAB/ Simulink. Setelah pemasangan filter Single Tuned Passive Filter Nilai arus harmonisa orde ke-3 berkurang dari 47,69 % menjadi 7,08 % tereduksi sebesar 40,61 %.en_US
dc.language.isoiden_US
dc.publisherUniversitas Sumatera Utaraen_US
dc.subjectSingle Tuned Passive Filteren_US
dc.subjectUPS Harmoniken_US
dc.subjectUPS Satu Fasaen_US
dc.titleReduksi Harmonisa pada Uninterruptible Power Supply (UPS) dengan Single Tuned Passive Filteren_US
dc.typeThesisen_US
dc.identifier.nimNIM127034013
dc.description.pages79 Halamanen_US
dc.description.typeTesis Magisteren_US