dc.contributor.advisor | Pinem, Maksum | |
dc.contributor.advisor | Rambe, Ali Hanafiah | |
dc.contributor.author | Nasution, Agus Almi | |
dc.date.accessioned | 2021-07-05T07:33:52Z | |
dc.date.available | 2021-07-05T07:33:52Z | |
dc.date.issued | 2016 | |
dc.identifier.uri | http://repositori.usu.ac.id/handle/123456789/34518 | |
dc.description.abstract | Using non-linier load in Uninterruptible Power Supply (UPS) can cause harmonic distortion which will eventually have the effect on power quality. The research was designed as a single-turned passive filter to cope will harmonic distortion in UPS. In this phase, THDv, THDi, and IHDi were measured in UPS. MATLAB/Simulink was used for simulation of filter testing. After single-turned passive filter was installed, the third order of harmonic current decreased from 47,69% to 7,08% or reduced 40.61%. | en_US |
dc.description.abstract | Penggunaan beban non linier pada Uninterruptible Power Supply (UPS) mengakibatkan distorsi harmonik yang berdampak pada kwalitas daya. Penelitian ini, dirancang sebuah single-tuned passive filter untuk mengatasi distorsi harmonik pada UPS. Pada tahapan ini dilakukan pengukuran THDv, THDi, dan IHDi pada UPS. Simulasi ujicoba filter menggunakan MATLAB/ Simulink. Setelah pemasangan filter Single Tuned Passive Filter Nilai arus harmonisa orde ke-3 berkurang dari 47,69 % menjadi 7,08 % tereduksi sebesar 40,61 %. | en_US |
dc.language.iso | id | en_US |
dc.publisher | Universitas Sumatera Utara | en_US |
dc.subject | Single Tuned Passive Filter | en_US |
dc.subject | UPS Harmonik | en_US |
dc.subject | UPS Satu Fasa | en_US |
dc.title | Reduksi Harmonisa pada Uninterruptible Power Supply (UPS) dengan Single Tuned Passive Filter | en_US |
dc.type | Thesis | en_US |
dc.identifier.nim | NIM127034013 | |
dc.description.pages | 79 Halaman | en_US |
dc.description.type | Tesis Magister | en_US |