dc.description.abstractCurrent transformer, which is used for measurement and protection, can produce harmonics that usually causes problems such as the equipment does not function and the current is cut off from network. The result of the measurement showed that the harmonic data in Current Individual Harmonic Distortion (IHDi) of order-5 in the current transformer was 12%. The result of the simulation showed that using passive single-tuned filter could reduce IHDi order-5 from 23.81% to 1.14% and THDi from 24.8% to 4.64%.en_US
dc.description.abstractTransformator arus yang digunakan untuk pengukuran dan proteksi dapat menghasilkan harmonik yang biasanya menyebabkan masalah seperti tidak berfungsinya peraltan dan dan kehilangan sambungan di jaringan. Dari pengukuran yang dilakukan, terdapat data harmonik pada Current Individual Harmonic Distortion (IHDi) orde-5 pada transformator arus sebesar 12%. Dari hasil simulasi yang dilakukan dengan menggunakan passive single-tuned filter dapat menurunkan IHDi orde-5 dari 23,81% menjadi 1,14% dan THDi dari 24,8% menjadi 4,64%.en_US
dc.language.isoiden_US
dc.publisherUniversitas Sumatera Utaraen_US
dc.subjectTransformator arusen_US
dc.subjectHarmoniken_US
dc.subjectCurrent Individual Harmonic Distortion (IHDi)en_US
dc.subjectPassive Single-Tuned Filteren_US
dc.titlePerancangan Passive Single Tuned Filter untuk Mereduksi Harmonik Arus pada Transformator Arus akibat Beban Nonlinieren_US
dc.identifier.nimNIM107034001
dc.description.pages85 Halamanen_US