Analisis Perbandingan Metode Fuzzy Logic dengan Metode Forward Chaining dalam Diagnosis Gangguan pada Transformator 150 KV menggunakan Dissolved Gas Analysis (Dga)
View/ Open
Date
2022Author
Supriyadi
Advisor(s)
Syafruddin
Pinem, Maksum
Metadata
Show full item recordAbstract
The gas contained in transformer oil is difficult to identify directly because
the formation of gas takes a long time with temperatures above 140 ºC. The gases
produced due to the increase in temperature in the transformer follow the order of
Hidrogen (H2), Methane (CH4), Ethylene (C2H4), Ethane (C2H6), and Acetylene
(C2H2). The Dissolved Gas Analysis (DGA) method used in this study was TDCG
(Total Dissolved Combustible Gas) according to the IEEE std C57.104, Duval
Triangle, Basic Gas, and CO2/CO standards according to IEC 60599-2007-05
standards as well as fuzzy logic and forward methods chaining. Based on theDGA
(Dissolved Gas Analysis) analysis of two transformers, namely Transformer G.T
2.1 and ST-01. Based on the fuzzy logic method with TDCG and Duval, the G.T 2.1
transformer is still in condition 2 and experiences thermal disturbances at T1 and
T2 levels with deffuzification values of 6.5 and 8. For transformers ST-01 is still in
condition 1, which is a normal state with diagnosed disorders, namely PD and T1.
While the forward chaining method, can only identify disturbances in the G.T 2.1
transformer in the first sample with D1 (Discharge of low energy) interference, but
for the second to fourth samples as well as samples from the ST-01 Transformer,
the diagnosis of the disorder cannot be identified. Gas yang terdapat dalam minyak transformator sukar diidentifikasi secara
langsung dikarenakan terbentuknya gas membutuhkan waktu yang cukup lama
dengan suhu diatas 140 ºC. Gas yang dihasilkan akibat peningkatan suhu pada
transformator mengikuti urutan yaitu Hidrogen (H2), Metana (CH4), Etilen (C2H4),
Etana (C2H6), dan Asetilen (C2H2). Metode Dissolved Gas Analysis (DGA) yang
dipakai pada penelitian ini adalah TDCG (Total Dissolved Combustible Gas)
menurut standar IEEE std C57.104, Duval Triangle, Basic Gas, dan CO2/CO
menurut standar IEC 60599-2007-05 serta metode fuzzy logic dan forward
chaining. Berdasarkan hasil analisis DGA (Dissolved Gas Analysis) terhadap dua
transformator yaitu Transformator G.T 2.1 dan ST-01. Berdasarkan metode fuzzy
logic dengan TDCG dan Duval, transformator G.T 2.1 masih dalam kondisi 2 serta
mengalami gangguan termal pada level T1 dan T2 dengan nilai deffuzifikasi 6,5
dan 8. Untuk Transformator ST-01 masih dalam kondisi 1 yaitu keadaan normal
dengan gangguan yang diagnosa yaitu PD dan T1. Sedangkan metode forward
chaining, hanya dapat menidentifikasi gangguan pada transformator G.T 2.1 pada
sampel pertama dengan gangguan D1(Discharge of low energy), tetapi untuk
sampel kedua hingga keempat serta sampel dari Transformator ST-01, diagnosis
gangguan tidak dapat teridentifikasi.