Studi Pengurangan Harmonisa Arus pada Power Amplifier dengan Menggunakan Filter Passtve Single Tuned
View/ Open
Date
2015Author
Syahrizal, Edi
Advisor(s)
Suherman
Rambe, Ali Hanafiah
Metadata
Show full item recordAbstract
Nowadays, non-linear load is increasingly used in industry or in households. The use
of non-Iinear load such as Power Amplifier can cause harmonics disorder in the
system. The phenomena of harmonics can cause sinusoidal wave to become non simtsoidal, especially in source curuent wcve. The amotmt of harmonics value which --
exceeds the limit can ccruse damage in the other electric equipment. Various attempts
have been made to improve the quali4t of power and to minimize the harmonics by
using harmonic fihers. One of them is Passive Single Tanedfilter which is used in
this research. The resalt of filter design in this research was to dampen harmonics so
that it could improve current harmonics caused by on-linean load. The resalt of the
research showed that some odd-order harmonics had exceeded IEC harmonic
stondnrd 6100A4-2; one af them was order 3-37. The result of the calculation
showed that R-value : 0.26 8, L : 0.28 H, and c : 4.0283.10-5 F; all of them would
be arranged in a series in order to reduce harmonics. The result of the simulation
showed that they could ffictively reduce harmonic content from 75.8% to 9.72%.
Collections