Analisis Pemulihan Kedip Tegangan Akibat Gangguan Fasa Ke Tanah dengan Menggunakan Dynamic Voltage Restorer pada Sistem Tiga Fasa dengan Beban Sensitif Bervariasi
View/ Open
Date
2012Author
Gultom, Golfrid
Advisor(s)
Baafai, Usman S
Dinzi, Riswan
Metadata
Show full item recordAbstract
Electrical power quality problem is very important to solve. The emergence of
voltage sags both its duration and depth greatly affects the performance of sensitive
equipment. The emergence of voltage sag is due to, the disturbance in the power
system either in transmission networks, distribution networks, and motor starter with
big power or energizing transformer. This study was to analyze the voltage sag
recovery occurred due to the disturbance in one-phase to the earth of three-phases to
protect the sensitive equipment by using Dynamic Voltage restorer (DVR) with PI
controller. To detect the emergence of voltage sag, Park Transformation implemented
in voltage regulator system which will continuously detect the voltage in the sensitive
load was used. The result of this study showed that DVR can restore the voltage sag
caused by the disturbance of one-phase to earth with the recovered voltage of I pu
without affecting the undisturbed phase in voltage recovery time of 0.1 ms. From this
result of study, it is found out that the amount of protected load power will affect the
amount of output voltage of inverter and injection through the LC passive filter.