Show simple item record

dc.contributor.advisorBaafai, Usman S
dc.contributor.advisorRamli, Marwan
dc.contributor.authorPasaribu, Faisal Irsan
dc.date.accessioned2023-07-12T04:08:49Z
dc.date.available2023-07-12T04:08:49Z
dc.date.issued2014
dc.identifier.urihttps://repositori.usu.ac.id/handle/123456789/85833
dc.description.abstractThe use of non-linear load in ceragem (a type of thermal acupuncture device) can cause harmonic distortion which will have the effect on bad quality of power. This research designed a single-tuned passive filter for handling harmonic distortion in ceragem material at the temperature of 60° C. Some conducted stages were to identify the type of temperature load of 30 °c, 40 °c, 50 °c, and 60 °c in ceragem by measun·ng harmonics and to perform simulation for filter trial by using Matlah/Simulink. From the result of the test, it was found that the designed filter could function well; from the test of ceragem load at the temperature of 60 °C, it was found that the reduction of harmonic current was from 133.8 % to 17 %.en_US
dc.language.isoiden_US
dc.publisherUniversitas Sumatera Utaraen_US
dc.subjectSingle-tuned Passive Filteren_US
dc.subjectCeragem Harmonicsen_US
dc.subjectTemperatureen_US
dc.subjectSDGsen_US
dc.titleMereduksi Harmonisa pada Alat Terapi Ceragem dengan Single Tuned Passive Filteren_US
dc.typeThesisen_US
dc.identifier.nimNIM127034009
dc.identifier.nidnNIDN0022104601
dc.identifier.kodeprodiKODEPRODI20101#Teknik Elektro
dc.description.pages73 Halamanen_US
dc.description.typeTesis Magisteren_US