dc.description.abstractPower transformer is one of the vital tools in the electrical power system that requires proper maintenance for its smooth operation. The transformer cannot be separated from the possibility of abnormal conditions that lead to disturbances. The disturbances that usually occur are thermal failure and electrical failure in the transformer insulation. Disturbances in the transformer can be indicated by the presence of gases dissolved in transformer oil, such as H2, CH4, C2H2, C2H4, C2H6, CO, and CO2. One method used to identify disturbances in transformer oil is DGA, also known as dissolved gas analysis. The dissolved gases formed in the transformer oil can provide important clues about the operational condition and integrity of the transformer. In this study, the interpretation of IEEE std C57.104-2008 and IEC 60599-2015 is used. The methods used for DGA testing based on the interpretation of IEEE std C57.104-2008 are TDCG method, key gas method, and Rogers ratio method. The methods used for DGA testing based on the interpretation of IEC 60599-2015 are Duval triangle method, basic gas ratio method, and ratio CO2/CO method. The analysis results indicate that the TNP-4 power transformer of PT INALUM (Persero) experiences an increase in temperature above normal.en_US
dc.language.isoiden_US
dc.publisherUniversitas Sumatera Utaraen_US
dc.subjectPower Transformeren_US
dc.subjectDGAen_US
dc.subjectTransformer Oilen_US
dc.subjectGas Ratioen_US
dc.subjectTransformer Oil Failureen_US
dc.subjectSDGsen_US
dc.titleDiagnosis Minyak Transformator dengan Analisis Gas Terlarut Menggunakan Metode Pas ( Photo-Acoustic Spectroscopy) Studi Kasus : PT. Inalum (Persero)en_US
dc.typeThesisen_US
dc.identifier.nimNIM190402181
dc.identifier.nidnNIDN0001075904
dc.identifier.kodeprodiKODEPRODI20201#Teknik Elektro
dc.description.pages116 Halamanen_US
dc.description.typeSkripsi Sarjanaen_US


Files in this item

Thumbnail
Thumbnail

This item appears in the following Collection(s)

Show simple item record