    Pengaruh Polutan Fly Ash Batu Bara pada Isolator Polymer Silicone Rubber 20 kV Tipe Tumpu dan Tarik terhadap Arus Bocor dengan Variasi Kelembapan Udara

    Effect of Coal Fly Ash Pollutants on A 20 kV Polymer Silicone Rubber Isolator of Fulcrum and Tensile Type on Leakage Current with Variations in Air Humidity

    Thumbnail
    View/Open
    Cover (1.681Mb)
    Fulltext (3.335Mb)
    Date
    2024
    Author
    Damanik, Muhammad Raihan Fauzi
    Advisor(s)
    Zulkarnain, Hendra
    Metadata
    Show full item record
    Abstract
    Fly ash is ash waste resulting from the residue of coal combustion at PLTU. Fly ash can fly in the wind and then stick to the surface of the insulator around the power plant. Fly ash pollutants that contaminate the surface of this insulator can make the surface of the insulator conductive so that leakage current will arise through the surface of the insulator. In this study, tests were carried out to analyze leakage currents in Polymer Silicone Rubber Insulators that are influenced by fly ash pollutants and air humidity. The results of the test found that the value of leakage current in insulators in clean conditions was in the range of 11.33 - 12.4 μA. After the pollutants are applied to the insulator surface with a light weight, the leakage current is in the range of 15.63 - 19.66 μA, in medium weight it is in the range of 16.73 - 20.4 μA and in heavy weight it is in the range of 17.2 - 22.26 μA. It can be seen from the results obtained, the more increased the weight of the pollutants given, the leakage current will increase. Meanwhile, at air humidity 75% RH leakage current is in the range of 15.63 - 17.73 μA, at 80% RH leakage current is in the range of 16.3 - 19.63 μA, at 85% RH leakage current is in the range of 17.56 - 20.46 μA and at 90% RH leakage current is in the range of 19.03 - 22.26. From the results obtained, it is known that if the air humidity increases, the leakage current in the insulator also increases
    URI
    https://repositori.usu.ac.id/handle/123456789/95236
    Collections
    • Undergraduate Theses [1464]

    Repositori Institusi Universitas Sumatera Utara (RI-USU)
    Universitas Sumatera Utara | Perpustakaan | Resource Guide | Katalog Perpustakaan
    DSpace software copyright © 2002-2016  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    Atmire NV
     

     

    Browse

    All of USU-IRCommunities & CollectionsBy Issue DateTitlesAuthorsAdvisorsKeywordsTypesBy Submit DateThis CollectionBy Issue DateTitlesAuthorsAdvisorsKeywordsTypesBy Submit Date

    My Account

    LoginRegister

    Repositori Institusi Universitas Sumatera Utara (RI-USU)
    Universitas Sumatera Utara | Perpustakaan | Resource Guide | Katalog Perpustakaan
    DSpace software copyright © 2002-2016  DuraSpace
    Contact Us | Send Feedback
    Theme by 
    Atmire NV