Show simple item record

dc.contributor.advisorZulkarnain, Hendra
dc.contributor.authorAzzura, Azzura
dc.date.accessioned2024-08-23T09:11:23Z
dc.date.available2024-08-23T09:11:23Z
dc.date.issued2024
dc.identifier.urihttps://repositori.usu.ac.id/handle/123456789/96071
dc.description.abstractA breakdown of lightning arresters occurred from 2021 to 2023 in the Raw Mill and Kiln Outlet areas on the Medium Voltage Switchgear (MVS) at PT. Solusi Bangun Andalas (Lhoknga – Aceh Besar). This study aims to investigate the causes and impacts of lightning arrester failures at PT. Solusi Bangun Andalas and evaluate their maintenance. Using problem-solving methods such as Pareto Diagram, Fish Bone Diagram, Brainstorming, and Decision Making to analyze. The results from the Pareto Diagram theory (20-80%) showed that the issues at PT. Solusi Bangun Andalas were 11.8% due to lack of maintenance and 88.2% due to the arrester's lifetime, given that the arrester had been in operation for 15 years. The Fish Bone Diagram theory results indicated that the problem was caused by the type of lightning arrester using jointing cables. Brainstorming results suggested that routine maintenance should include replacing with the jointing busbar type and installing a surge counter. The impact of the damage focused on the output section of the electrical installation from circuit breaker, while irregular maintenance and the lack of surge counters on the lightning arrester were also identified. A deep understanding of this issue is essential for developing more efficient maintenance methods and improving the reliability of industrial electrical systemsen_US
dc.language.isoiden_US
dc.publisherUniversitas Sumatera Utaraen_US
dc.subjectPT. Solusi Bangun Andalas (Lhoknga – Aceh Besar)en_US
dc.subjectLightning Arresteren_US
dc.subjectMedium Voltage Switchgear (MVS)en_US
dc.subjectProblem Solvingen_US
dc.subjectSDGsen_US
dc.titleAnalisis Kerusakan Lightning Arrester pada Pabrik Semen PT. Solusi Bangun Andalas (Lhoknga – Aceh Besar)en_US
dc.title.alternativeAnalysis of Lightning Arrester Damage at PT. Solusi Bangun Andalas Cement Plant (Lhoknga – Aceh Besar)en_US
dc.typeThesisen_US
dc.identifier.nimNIM200402005
dc.identifier.nidnNIDN0014056104
dc.identifier.kodeprodiKODEPRODI20201#Teknik Elektro
dc.description.pages88 Pagesen_US
dc.description.typeSkripsi Sarjanaen_US