dc.description.abstractIn transmission lines, corona discharge has become one of the main issues causing power outages in our society, and it is important to pay attention to this phenomenon called corona. Corona is a discharge phenomenon caused by increased air ionization along the conductor. Calculations are performed using the mathematical methods of Peek and Peterson. This study aims to analyze the power loss caused by corona in transmission lines in mountainous and urban areas and to compare the two calculation methods. Technical data from PT PLN UP2B Sumbagut and temperature data from The Weather Channel website are used to calculate the power loss due to corona. The Research results show that the power loss due to corona is greatest in the mountainous area (Titikuning-Berastagi) compared to the urban area (Binjai-Payageli). This is because the air pressure in the mountainous region is lower, resulting in more humid conditions, which leads to a higher corona power loss. The magnitude of corona loss in a transmission line is influenced by factors such as temperature, air pressure, line length, phase spacing, and conductor diameter. Calculations using the Peterson method are simpler compared to the Peek method; however, the Peterson method is more accurate than the Peek methoden_US
dc.language.isoiden_US
dc.publisherUniversitas Sumatera Utaraen_US
dc.subjectCoronaen_US
dc.subjectPeeken_US
dc.subjectPetersonen_US
dc.subjectTransmission Linesen_US
dc.subjectLossesen_US
dc.subjectSUTT 150kVen_US
dc.subjectSDGsen_US
dc.titleAnalisis Saluran Transmisi di Daerah Pegunungan (Sutt 150kV Titi Kuning - Berastagi) dan Saluran Transmisi di Daerah Perkotaan (Sutt 150kv Binjai Payageli) terhadap Rugi Rugi Daya Akibat Korona Menggunakan Metode Peek dan Petersonen_US
dc.title.alternativeAnalysis of Transmission Lines in Mountainous Areas (150kV Sutt Titi Kuning - Berastagi) and Transmission Lines in Urban Areas (150kv Sutt Binjai - Payageli) Against Power Losses Due to Corona Using Peek and Peterson Methodsen_US
dc.typeThesisen_US
dc.identifier.nimNIM200402109
dc.identifier.nidnNIDN0009077806
dc.identifier.kodeprodiKODEPRODI20201#Teknik Elektro
dc.description.pages95 Pagesen_US
dc.description.typeSkripsi Sarjanaen_US


Files in this item

Thumbnail
Thumbnail

This item appears in the following Collection(s)

Show simple item record